6. TECHNICAL DATA
Basic parameters:
- analog output galvanicaly isolated:
- current 0/4...20 mA
- voltage 0...10 V
- maximal load resistance of the
current output £ 500 W
- minimal load resistance of the
voltage output ³ 500 W
- accuracy class
1)
0.2
- averaging time of the transducer:
- range: d.c. current [mA], d.c. voltage [V] ³ 0.1 s
- other ranges ³ 0.3 s
- consumption < 2 VA
- preheating time of the transducer 10 min
- transducer response time:
- range: d.c. current [mA], d.c. voltage [V] ³ 0.2 s
- other ranges ³ 0.4 s
- current flowing through RTD < 0.2 mA
- resistance of wires connecting
RTD with the transducer £ 10 W
Rated operating conditions:
- supply depending on the
execution code 85... 253 V a.c./d.c.
20...85 V d.c., 20...65 V a.c.
- frequency of the supply a.c. voltage 45... 65 Hz
- ambient temperature – 20...23...55°C
- storage temperature – 25...85°C
- related air humidity < 95% (condensation
inadmissible)
- working position any