CDA3000 Operation Manual
4-9
4  Commissioning
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
Set lines per revolution of  
encoder used
This setting is only required in “FOR” mode. 
 
Test setting
Attention: Make sure that the rotating drive of your machine cannot 
cause any damage during commissioning (such as by 
overshooting a stop limit) and that there are no personnel 
inside the danger zone.
 
In the last step you can adapt the 
basic setting of the preset solution 
to your application. 
The setting options vary according 
to the selected preset drive 
solution (here the example for 
ROT_2).
Step Action Note
1
Close ENPO contact. ENPO active enables power stage.
2
Set low reference with R1. 
see section “3.7.5 Terminal 
assignment 3”
3
Start drive by closing STL or STR 
contact.
Motor accelerates to preset reference
4
If the motor runs uncontrolled and does 
not accelerate up to the preset 
reference, stop the drive (open STL or 
STR contact).
Check phase position, motor and 
encoder connections, see section 4.5 
“Direction check”
Motor accelerates up to preset 
reference
,  commissioning can be 
continued.
5
Set correction reference with R2
Drive accelerates further by amount 
of correction reference.
4. Change basic settings...