4-22
CDA3000 Operation Manual
4 Commissioning
4.8 Parameter list
(selection)
1) Setting dependent on device. 2) Setting dependent on motor. 3) Selection, not complete
Name Unit Function
Factory
setting
Your setting
Subject area
Initial commissioning _15FC
150-SAVE - Back-up device setup READY
151-ASTPR - Original device preset DRV_1
152-ASTER - Preset terminal assignment DRV_1
154 -MOPNM kW Motor rated power 1)
155 -MOVNM V Motor rated voltage 1)
156-MOFN Hz Motor rated frequency 50
157 -MOSNM rpm Motor nominal speed 2)
158 -MOCNM A Motor rated current 2)
159 -MOCOS - Motor cos-phi 0.8
163-ENSC - Motor auto-tuning STOP
164-UMWR -
Back-up device setup in a user
mode
1
165-UMAC - Activate user mode 1
166-UMSEL -
Control location for switchover of
active user mode
PARAM
167-SCPRO - Auto-tuning progress indicator 0
300-CFCON - Current control mode VFC
Subject area
Fixed frequencies _15FC
270-FFIX1 Hz Fixed frequency 20
Subject area
Frequency limits _30OL
301-FMIN1 Hz Minimum frequency 0
303-FMAX1 Hz Maximum frequency 50
Subject area
Motor protection _33MO
330-MOPTC - Type of motor PTC evaluation OFF
Subject area
Driving profile generator _59DP
590-ACCR1 Hz/s Acceleration ramp 20
592-DECR1 Hz/s Deceleration ramp 20
594-STPR1 Hz/s Stop ramp 20
Subject area
Encoder evaluation _79EN
790-ECLNC
Pulses
per rev
Lines per revolution of encoder 1024
Subject area
Analog inputs _18IA
180-FISA0
Settings
3)
for analog input ISA00:
OFF = Not active
0-10V = Voltage input 0...10 V
PM10V = Voltage input -10 V...+10 V
0-20 = Current input 0...20 mA
4-20 = Current input 4...20 mA
OFF

Other manuals for Lust CDA34.017