CDD3000-HF Operation Manual
3-15
3  Installation
DE
EN
FR
IT
ES
FR
1
2
3
4
5
A
Mains filters
 
Note: Compliance with the limit curves to attenuate the line-borne 
interference voltage and the interference emitted from the 
CDD3000-HF drive controller depends on
· use of a line choke (recommended),
· the length of the motor cable and
· the pre-set clock frequency (4, 8, 12 or 16 kHz) of the
  CDD3000-HF drive controller power stage. For further
  information please contact your project engineer.
Wire cross-section
.
1)
 The minimum cross-section of the mains power cable is based on the local
provisions (VDE 0100 Part 523, VDE 0298 Part 4), the ambient temperature
and the specified rated current of the CDD3000-HF drive controller.
Size Power range Mains filter
BG1 ... 4 1.0 ... 11.8 kVA Internal
1) For supplementary components see CDD3000-HF Order Catalogue
drive controller for 
highspeed drives
Connection
load
[kVA]
Max. possible wire 
cross-section of 
terminals [mm²]
Recommended mains 
fusing (gL)
[A]
CDD32.003-HF
CDD32.004-HF
1.0
1.7
2.5
1 x 10
1 x 10
CDD32.006-HF
CDD32.008-HF
CDD34.003-HF
CDD34.005-HF
2.3
3.0
1.6
3.0
2.5
1 x 16
1 x 16
3 x 10
3 x 10
CDD34.006-HF 4.2 2.5 3 x 10
CDD34.008-HF
CDD34.010-HF
5.7
7.3
2.5
3 x 10
3 x 16
CDD34.014-HF
CDD34.017-HF
10.2
12.4
4.0
3 x 20
3 x 25
CDD34.024-HF
CDD34.032-HF
17.5
23.3
10
3 x 35
3 x 50
Table 3.8 Wire cross-sections and mains fuses (conformance to VDE 
0298 is required)
1