Step by Step instructions for GRAFIK Eye Dimming Panel
14
Assign Load Types
Circuit Selector
A,F
SELECT VALUE
VIEW VALUE
SELECT VALUE DISPLAYED
Load Type
(See Instructions)
High-End Trim
Circuit Level
Low-End Trim
5
4
3
Zone Assignment w/
Circuit Schedule
Zone Assignment w/
Zone Capture
TM
Link A
Link B
Address (Ad displayed)
SELECT CIRCUIT
2
1
Circuit
Common
24VFW
MUX
MUX
Drain
Sense
1234
D
5
Value
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
SELECT VALUE
VIEW VALUE
SELECT VALUE DISPLAYED
Load Type
(See Instructions)
High-End Trim
Circuit Level
Low-End Trim
5
4
3
Zone Assignment w/
Circuit Schedule
Zone Assignment w/
Zone Capture
TM
Link A
Link B
Address (Ad displayed)
SELECT CIRCUIT
2
1
Circuit
Common
24VFW
MUX
MUX
Drain
Sense
1234
D
5
Value
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
C
D
STEP 10: Assign Load Types
Assigning Load Types is done using the Circuit Selector located in
each GP panel.
To view present load types:
Press button 5 to step through the Value displays until Load
Type LED lights. Use buttons 1 and 2 to view present load type of
each circuit. Note that ‘ - - - ’ in the Value display means a Load
Type is not assigned to the circuit.
If load types are already assigned, compare them to the Circuit
Directory (if provided). If there are no changes to be made, go to
Step 11.
To change load types:
A. Press and hold buttons 1 and 5 until SELECT VALUE LED
blinks once per second.
B. Press button 5 to step through the Value displays until the
Load Type LED lights.
C. Choose circuit number with buttons 1 and 2.
D. Use buttons 3 or 4 to choose the appropriate Load Type (see
below for Load Type Display).
E. Repeat Steps C and D for each circuit.
F. Press and hold buttons 1 and 5 until the VIEW VALUE LED
lights.
Notes:
The Value window will display the software revision level of
the Circuit Selector 20 minutes after the last button press.
Mark all changes to the Circuit Selector’s values on a Circuit
Directory for future reference.
Load Type Display
- - - Unassigned (All intensities except 0 = On)
1 - 1 Incandescent, Tungsten
2 - 1 Fluorescent: Lutron Hi-Lume® FDB or Eco-10™
2 - 2 Fluorescent: Lutron Tu-Wire™
2 - 3 Fluorescent: 0-10V, with TVM module
2 - 4 Fluorescent: PWM, with TVM module
2 - 5 Fluorescent: Tridonic® DSI, with TVM module
3 - 1 Neon/Cold Cathode
4 - 1 Non-Dim: All intensities except 0 = On
4 - 2 Non-Dim: Intensities above 60% = On, below 40% = Off
5 - 1 Electronic Low Voltage
6 - 1 Magnetic Low Voltage
Warning! Failure to correctly assign Load Type may
damage loads–especially certain Electronic Transformers,
Electronic Ballasts, and Motors. Verify with transformer or
ballast manufacturer that product can be dimmed with
phase control dimming before setting to any Load Type
other than Non-Dim.