Reference Sheets for GRAFIK Eye Dimming Panel
28
Circuit Selector
Functions
Reference Sheet
The Circuit Selector can also provide or receive a ‘sense’ line
depending on the location of Switch 6 (SW6).
Circuit Selector Functions
There is a Circuit Selector in every Lighting Control Panel. It is used
to communicate with GRX-4000 Series Control Unit(s), G6000
controller, or DMX512 stageboards – and then to tell the dimmers
their intensity levels.
It is also used to select Values for each Circuit:
■ Circuit Level - allows a way to view the intensity being sent to
the dimmer or manually take over control of the dimmer’s output.
See description in the Troubleshooting Reference section.
■ Load Type - to be changed to match the load to the Load Type
value. Non-Dim 4 must be used if the Load is not dimmable.
■ Control and Zone Assigned - allows two ways of assigning a
control and zone to a specific circuit.
1. ‘w/ Circuit Schedule’ allows a Control and Zone (such as
‘A2’,‘3’) to be directly entered into the Circuit Selector.
2. ‘w/
Zone Capture
™” allows a Control and Zone to be
‘captured’ by the Circuit Selector by doing the following:
A. Press and hold buttons 1 and 5 until the SELECT
VALUE LED lights.
B. Press button 5 repeatedly until the
Zone Capture
™
LED lights. The circuit will now flash.
C. Use buttons 1 and 2 to choose the correct circuit to be
assigned.
D. Go to the GRX-4000 Series Control Unit to be assigned
to this circuit.
E. Select Scene 1.
F. Identify the zone to be assigned to this circuit.
G. Press the zone 6 button until all zone LEDs are off.
H. Press the zone 5 button until the load starts tracking
the zone intensity LEDs.
I. Press the zone 6 button until all zone LEDs are off.
(Steps H. and I. must take less than 15 seconds or the
Circuit Selector will not lock on the captured zone.)
J. Go back to the Circuit Selector and the proper Control
and Zone should be displayed.
Repeat this process for any other Circuits.
K. Press and hold buttons 1 and 5 until the VIEW VALUE
LED lights.
■ Low and High End Trims - allows the Circuit’s range limits to
be adjusted.
‘Power OK’ indicates whether
24VAC is present from the Class
2 transformer.
‘Data OK’ LED(s) blink when
the Circuit Selector is properly
receiving data.
SW6