Step by Step Instructions for GRAFIK Eye Dimming Panel
5
Wire System
Incorrect: Branch or Home Run not acceptable
GP
PANEL
GP
PANEL
To other panels, GRX-4000 Series Control Units,
Wallstations, or Control Interfaces.
Control
Interface
GRX-4000
Wallstation
STEP 3: Control Wiring
Control Link Specifications
Questions on wiring?
Lutron may be able to help with charts of Wallstations
versus distance.
Total length of Control Link may be no more than 2,000 feet. This
distance is based on proper shielding on the twisted shielded pair,
and on #12 AWG wire on the wires to terminal 1 and terminal 2 of
the Control Link. If unapproved cable or smaller wire is used, this
limit is affected:
Total number of Wallstations, Control Units, Control Interfaces or
Circuit Selectors = 33 maximum.
Total number of Control Unit addresses = 8 maximum
Note: GRX-4116/4516 has 2 addresses
GRX-4124/4524 has 3 addresses
Total number of Wallstation or Control Interface addresses = 16
maximum.
Notes:
■ Make wire connections inside the wallbox and GP panel or in a
junction box (by others) within 8 ft. (2.4 m) of the terminal.
■ All control wiring is Class 2/PELV. Do not place any of these
wires in with line voltage (mains voltage) wiring.
■ The order of controls within the control wiring is not important.