EasyManua.ls Logo

Lutron Electronics Switch - Branch Circuit Breaker Panel Wiring

Lutron Electronics Switch
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R
Installation Guide for Switching Panels 11
Wiring
(continued)
H
SH
H
SH
H
SH
H
SH
H
SH
Panel with Branch Circuit Breakers: Feed and Load Wiring
(120/277/347 V only)
Bypass jumpers -
do not remove
Load
Neutral bus
Neutral bus
Main lugs
Branch circuit
breakers for
temporary
lighting
Wiring Tips
Wire the switching panel similar
to wiring a lighting distribution
panel:
Run feed and load wiring. No
other wiring or assembly
required.
The switching panel can provide
temporary lighting:
Wire all loads.
Leave the bypass jumpers in
place.
Use branch circuit breakers at
the distribution panel to switch
lights on and off.
Wire Sizes
120 V #4 AWG to 250 KCMIL (MCM) (25-185 mm
2
)
277 V #4 AWG to 250/350 KCMIL (MCM) (25-120/185 mm
2
)
347 V #4 AWG to 250/350 KCMIL (MCM) (25-120/185 mm
2
)
Feed Wiring
Switched Hot/Live
#14-#10 AWG
(2.5-4.0 mm
2
)
Load Neutral
#14-#10 AWG
(2.5-4.0 mm
2
)
Typical switch leg
XP12-1204ML-20 shown