E-Power
e-MM/MT 230V
Guida Utente User Manual
made in Italy
Cod. /620030200 Rev.10

Questions and Answers

  • N
    Nicholas StoneAug 19, 2025
    What to do if my MAC3 EPOWER-MM shows 'Imax Fault'?
    • K
      kennethmontgomeryAug 19, 2025
      If your MAC3 Inverter displays an 'Imax Fault', it indicates an overcurrent has been detected in the pump. Check the current measurement output at parameter 36 "LoadCurrent " and set the proper value of max. current at parameter 49. Ensure the pump operates within the manufacturer's specified conditions and that the impeller isn't experiencing friction or locking.
  • A
    Andrew RiveraAug 21, 2025
    What to do if MAC3 EPOWER-MM displays 'Manca acqua No water'?
    • A
      Andrew NelsonAug 21, 2025
      If your MAC3 Inverter shows 'Manca acqua No water', it means a lack of water was detected. Check for water presence and ensure the pump is correctly primed. Also, verify that the filter isn't blocked. Disconnect the power supply, wait for the display to switch off, and then reconnect the power supply.
  • E
    Elizabeth RangelAug 25, 2025
    What does 'Tensione alta High voltage' mean on my MAC3 EPOWER-MM Inverter, and how to fix it?
    • J
      janethortonAug 25, 2025
      If your MAC3 Inverter displays 'Tensione alta High voltage', it means the power voltage measured is too high (over 270 Vac). The reset is automatic when the voltage returns to the correct value. Check the wiring system and set the values in the range prescribed for the EPOWER. Check for the presence of air inside the pump and if necessary eliminate it.
  • J
    John MurrayAug 26, 2025
    How to troubleshoot 'Corto f-f ShortC. F-f' error on MAC3 EPOWER-MM Inverter?
    • J
      Julia LoganAug 26, 2025
      The 'Corto f-f ShortC. F-f' error on your MAC3 Inverter indicates a Phase-Phase or Phase-Ground short circuit. To resolve this, remove the short circuit, check the correct motor absorption, disconnect the power supply, wait for the display to switch off, and then restore the power supply.
  • R
    Richard BarryAug 28, 2025
    What does 'Tensione bassa.. Low Voltage' mean on MAC3 EPOWER-MM and how to solve it?
    • A
      amandabeckerAug 28, 2025
      If your MAC3 Inverter displays 'Tensione bassa.. Low Voltage', it indicates that the power voltage measured is too low (less than 170 Vac). The reset is automatic when the voltage returns to the correct values. Check the electric system and reset the values to within the range prescribed for the EPOWER.
  • M
    mariapattonAug 30, 2025
    Why does my MAC3 Inverter show 'Temp. Alta High Temp.'?
    • M
      Marc MacdonaldAug 30, 2025
      If your MAC3 Inverter displays 'Temp. Alta High Temp.', it means the water temperature is above 75 °C. It will automatically reset if the temperature drops below 60 °C. Ensure the water temperature is within the product specifications and restore the correct pump priming action.
  • J
    Jonathan FoxSep 1, 2025
    What to do if MAC3 EPOWER-MM displays 'Blocco Cortoc. Short Circ.Block'?
    • J
      jmeyerSep 1, 2025
      If your MAC3 Inverter displays 'Blocco Cortoc. Short Circ.Block', the drive is in a locked status after 10 reset attempts following a short circuit. To remove the lock status, set the number of shortcircuit parameter 65 "Tot.ShortC.Done " to zero. If the problem persists, try resetting the drive by unplugging the pump.
  • J
    Jennifer PowellSep 3, 2025
    What does 'Protetto per I2t I2t protected' mean on my MAC3 Inverter?
    • L
      Lee CampbellSep 3, 2025
      If your MAC3 Inverter displays 'Protetto per I2t I2t protected', it indicates that the drive has measured an excessive current. Verify that the pump is used under the conditions prescribed by its manufacturer. Make sure that there are no conditions of friction or locking of the impeller.
  • D
    Douglas WilsonSep 5, 2025
    Why does my MAC3 EPOWER-MM Inverter display 'Motore Sconnesso Motor Unconnected'?
    • L
      Laura Thompson MDSep 5, 2025
      If your MAC3 Inverter displays 'Motore Sconnesso Motor Unconnected', it means the pump isn’t connected to the inverter. Check that the power output cable from the inverter is connected to the pump.
  • K
    kidddavidSep 8, 2025
    What does 'Press. Insuff Insuff. Pres' mean on MAC3 EPOWER-MM and how can I fix it?
    • L
      Lisa RaySep 8, 2025
      If your MAC3 Inverter displays 'Press. Insuff Insuff. Pres', it indicates that the measured pressure is below the minimum set value (default 0,8 bar). Check that there is no major leakage on the system and verify the correct dimensions of the electro-pump. On eliminating the causes disconnect the power supply Wait for the display to switch off Restore power supply.

Summary

Avvertenze - Warning

Guida allacquisto - Guide to purchase

Scelta della pompa

Guide on selecting the correct pump for optimal Epower performance.

Adattatore per connessioni lunghe (ACL)

Recommends ACL filter for long cables to reduce overvoltages.

Filtri EMI

Mac3 inverters are EMI certified; additional filters available for sensitive environments.

Contenuto della confezione - Package contents

Guida Rapida per messa in funzione - Start Up procedure

Installazione Idraulica - Hydraulic Installation

Step-by-step guide for the hydraulic installation of the Epower unit.

Installazione elettrica - Electrical Installation

Step-by-step guide for the electrical installation of the Epower unit.

Installazione Software - Software Installation

Instructions for software installation and keyboard usage.

Generalità - General Remarks

Descrizione del Prodotto - Product Description

Overview of Epower as a variable speed drive for constant pressure systems.

Condizioni di Esercizio - Usage Condition

Specifies optimal operating temperature, humidity, and fluid conditions.

Caratteristiche Tecniche - Technical Features

Details technical specifications of the Epower unit, including power and dimensions.

Protezioni - Protections

Lists safety protections and their reset mechanisms for abnormal conditions.

Funzionamento ed Impiego - Functioning and Use

Collegamento idraulico - Hydraulic connection

Guidelines for proper hydraulic connection and expansion tank sizing.

Collegamento elettrico - Electrical Connection

Instructions for making electrical connections to the Epower unit's terminals.

Suggerimenti - Tips

Practical advice and recommendations for using the Epower unit.

Collegamenti aggiuntivi - Additional connections

Configurazione Galleggiante di minima - Dry running float Configuration

How to configure a float switch for dry running protection.

Configurazione Relè - Relay Configuration

Using the internal relay for alarms, pump operation, or booster control.

Configurazione Booster (pompa ON;OFF) - Booster Configuration (ON;OFF pump)

Details on configuring a second pump for ON/OFF operation.

Configurazione modalità Multipompa - Multipump Configuration

Steps to set up the Epower for multipump system operation.

Menu software - Software Menu

Ricerca Guasti e Manutenzione - Troubleshooting & Maintenance

Menu Esteso - Extended Menu

Tabella Parametri - Parameter Table

Comprehensive list of all configurable parameters and their settings.

DICHIARAZIONE DI CONFORMITÀ- CONFORMITY DECLARATION

MAC3 EPOWER-MM Specifications

General IconGeneral
BrandMAC3
ModelEPOWER-MM
CategoryInverter
LanguageEnglish