Madman EMS-3 Operating Manual Page 22
Message type=128
Data Length=29 bytes
Output Rate=1Hz
Unused channels will read 0
Hour Meter Hours: Unsigned Int (16 bits), Hour meter hours
Hour Meter Minutes: Unsigned char (8 bits), Hour meter minutes
Service Time: Unsigned Int (16 bits), Service time in hours
Volts: Unsigned Int (16 bits), Volts in 0.1V
Analog Channel Type: Unsigned Int (16 bits)
CH4 (4 bits), CH3 (4 bits), CH2 (4 bits), CH1 (4 bits)
0=Off
1=Pressure
2=Temperature
Analog Channel 1: Signed Int (16 bits)
Pressure in 0.1psi
Temperature in Degrees C
Analog Channel 2: Signed Int (16 bits)
Pressure in 0.1psi
Temperature in Degrees C
Analog Channel 3: Signed Int (16 bits)
Pressure in 0.1psi
Temperature in Degrees C
Analog Channel 4: Signed Int (16 bits)
Pressure in 0.1psi
Temperature in Degrees C
CJC: Signed Int (16 bit), Cold junction temperature in Degrees Celsius
EGT: Signed Int (16 bit), EGT in Degrees Celsius
RPM: Unsigned Long (32 bit), RPM value
RPM (%): Unsigned Int (16 bit), RPM value in percentage
CLD: Unsigned char (8 bits), 0=CLD alarm off, 1=CLD alarm on
Oil Pressure Switch: Unsigned char (8 bits), 0=Oil Pressure switch off, 1= Oil Pressure switch on