UDD-SD-112/ Release Date: 25.12.2014/Rev No: 1 /Rev. Date: 18.05.2015
4.6.5 Frequency Converter Mode Setting
1. CUCF mode only can be set in STDBY mode. In STDBY mode, enter the setting interface. Press
and hold the function setting key for more than 2 seconds, then come to setting interface,
Press and hold the inquiring key ( , ) for more than half a second(less than 2 seconds),
select the function setting, choose battery voltage setting interface, at the moment, the letters
“CF” will flash.
2. Enter the CF setting interface. Press and hold the function setting key for more than half
a second(less than 2 seconds), then come to setting interface of CF, at this time, the letters “CF”
will not flash any more. The “ON” (or OFF) will flash. Press and hold the inquiring key ( ,
) for more than half a second (less than 2 seconds) to determine whether the CF function is
used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can be
determined by yourself.
3. Confirm the CF selecting interface. After selecting ON or OFF, press and hold the function
setting key for more than half a second (less than 2 seconds). Now, the CF setting
function is completed and the “ON” or “OFF” will light without flash.
4. Exit from the setting interface. Press and hold function setting key for more than 2
seconds, exit from the setting interface and return to main interface.
5. After setting CF at “ON”, UPS would be back in STDBY Mode. The default value of CF is OFF.