FAN CYCLE CONTROL
FUNCTION
Cycles the fan motor on and off to maintain proper
operating discharge pressure.
The fan cycle control closes on an increase, and
opens on a decrease in discharge pressure.
SPECIFICATIONS
CHECK PROCEDURE
1. Verify fan motor windings are not open or
grounded, and fan spins freely.
2. Connect manifold gauges to ice machine.
3. Hook voltmeter in parallel across the fan cycle
control, leaving wires attached.
4. Refer to chart below.
Specifications
Model Cut-In (Close)
Cut-Out
(Open)
I0300 / I0320 I0520 /
I0450 / I0500 / I0600
I0660 / I0850 /
JC0995
250 ±5
(1723 kPa ±.34)
(17.23 bar ±.34)
200 ±5
(1517 kPa ±.34)
(15.17 bar ±.34)
I1000
I1400 / I1800
275 psig ±5
(1896 kPa ±34)
(18.96 bar±.34)
225 psig ±5
(1551 kPa ±34)
(15.51 bar ±.34)
FCC Setpoint:
Reading Should
Be:
Fan
Should Be:
Above Cut-In 0 Volts Running
Below Cut-Out Line Voltage Off

Table of Contents

Other manuals for Manitowoc b970 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc b970 series and is the answer not in the manual?

Manitowoc b970 series Specifications

General IconGeneral
BrandManitowoc
Modelb970 series
CategoryIce Maker
LanguageEnglish

Related product manuals