Part Number STH044 10/13 15
Electrical Service
General
Voltage
The maximum allowable voltage variation is ± 10% of
the rated voltage on the ice machine model/serial
number plate at start-up (when the electrical load is
highest).
Fuse/Circuit Breaker
A separate fuse/circuit breaker must be provided for
each ice machine. Circuit breakers must be H.A.C.R.
rated (does not apply in Canada).
CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select
the wire size of the electrical supply. (Minimum circuit
ampacity is not the ice machine’s running amp load.)
The wire size (or gauge) is also dependent upon
location, materials used, length of run, etc., so it must
be determined by a qualified electrician.
All wiring must conform to local, state and national
codes.
The ice machine must be grounded in accordance
with national and local electrical codes.
Self Contained Air-Cooled
Ice
Machine
Voltage
Phase Cycle
Max. Fuse/
Circuit
Breaker
Total
Amps
RNS012
RNS020
115/1/60 15 10.3
230/1/50 15 4.6