Refrigerant Recovery/Evacuation
NORMAL SELF-CONTAINED PROCEDURES
Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the
manufacturers recommendations.
CONNECTIONS
Manifold gauge sets must utilize low loss fittings to
comply with U.S. Government rules and regulations.
Make these connections:
Suction side of the compressor through the suction
service valve.
Discharge side of the compressor through the
discharge service valve.
Important
Manitowoc Ice assumes no responsibility for the use
of contaminated refrigerant. Damage resulting from
the use of contaminated refrigerant is the sole
responsibility of the servicing company.
Important
Replace the liquid line drier before evacuating and
recharging. Use only a Manitowoc (OEM) liquid line
filter-drier to prevent voiding the warranty.