222. Commissioning
2.6 Warning messages
When the automatic door operator detects a malfunction in the door operation, the program switch screen will show a
numeric code. The code interpretation is summarised in the following table:
Warning Possible cause Corrective action
02 SOS Emergency signal enabled. Check position of folding leaves.
Check emergency stop button.
03 Obstruction when
Closing
Obstruction during the closing cycle. Check that there are no obstructions
during closure.
04 Outside key switch The key has not be removed aer 1 min Remove the key from the outside key
switch device.
05 Parameter error Door parameter fault. Inform the Manusa Technical Service.
06 Obstruction when
Opening
Obstruction during the opening cycle. Check that there are no obstructions in the
opening area.
07 Photocell 1 Interior photocell blocked for more than 1
minute.
Clean the photocells. Should the
malfunction persist, inform the Manusa
Technical Service.
08 Photocell 2 Exterior photocell blocked for more than 1
minute.
Clean the photocells. Should the
malfunction persist, inform the Manusa
Technical Service.
09 Fire Fire alarm signal triggered. Check that it is not a false alarm. Should
the malfunction persist, inform the Manusa
Technical Service.
11 Batteries Battery not overly charged. If the door has been disconnected for
a while, connect it and wait 24 hours
for the batteries to charge. Should the
malfunction persist, inform the Manusa
Technical Service.
12 Interior Radar Interior radar detection more than 1
minute.
Inform the Manusa Technical Service.
13 Exterior Radar Exterior radar detection more than 1
minute.
Inform the Manusa Technical Service.
15 Auxiliary processor Communications failure with auxiliary
processor.
Should the malfunction persist, inform the
Manusa Technical Service.
16 Side safety device Detection of presence in the passage area
leaves for more than 1 minute
Check that there are no objects within the
detection radius of the sensor.
17 Lock Fault when attempting to close the lock. Inform the Manusa Technical Service.
22 Safety open Safety open sensor not configured Inform the Manusa Technical Service.
23 Safety close Safety close sensor not configured Inform the Manusa Technical Service.
24 Safety close Safety close sensor fault. Inform the Manusa Technical Service.
33 Current leakage Motor insulation fault. Inform the Manusa Technical Service.
34 Power module Power module stoppage due to
overcurrent or insulation fault.
Inform the Manusa Technical Service.
35 Encoder Encoder error. One of the two channels of
the encoder is faulty.
Inform the Manusa Technical Service.
36 Self-adjustment
fault
Self-adjustment not completed correctly. Inform the Manusa Technical Service.
49 Critical alarm Possible general fault in the motor control
microprocessor.
Inform the Manusa Technical Service.