Page 16 / 86 Technical Notice CSO/CPO V1.1 / 10.14
3 CPO 140 model
3.1.2 Technical specifications
3.1.2.1 Standard operating parameters
3.1.2.2 Electrical data
3.1.2.3 Air condenser
3.1.2.4 Evaporator
Description Unit CPO 140
Refrigerant Type R134A
Refrigerating capacity kW 1.4
Power consumption kW 0.7
Heat load kW 2.1
Inlet temperature °C 24
Outlet temperature °C 20
Max. input temperature °C 38°C
Description Unit CPO 140
Power input kW 0.8
Maximum amperage A 5
Start-up amperage A 13
Line fuse A T 10
Power supply V x ph x Hz 230 x 1 x 50
Description Unit CPO 140
Flow rate m3/h 580
Copper Alu w/ fins - X
Description Unit CPO 140
Pressure drops Pa 25
Stainless steel w/ rolled
plates
- X
Tubular stainless steel
(Cleanable)
-option