Page 58 / 86 Technical Notice CSO/CPO V1.1 / 10.14
9 Options
Settings (Omron E5CC)
The values shown below are given for information only.
Symbol Type Value
Adjustment
P Proportional strip 0.9
ITotal time65
d Diversion time 11
Setting
CN-T 1
dU °C
SL-H Max setpoint 35
SL-L Min setpoint 20
CNTL PID
S-HC Stnd
St OFF
Orew d
PtRN OFF
ALt1 Type 1 alarm 1
ALH1 Hysteresis 1
ALt2 Type 2 alarm 1
ALH2 Hysteresis 1
oiST Signal in mA 0-20
To access advanced functions:
AMoV Change the value from 0 to -169
Advanced functions
Sb1N N-C
Sb2N NO
At-H 0.1
Out 1 0
SUb1 High&Low temperature ALM 1
SUb2 ALM2
SUb3 NONE
Operation
Al-1H Too hot 10
Al-1L Too c o l d 10
Al-2H Too hot 10
Al-2L Too c o l d 10