OPERATION
24 Copyright © 2008 Mastervolt / December 2008 / Whisper 12 Ultra - Three phase for mobile applications/ EN
3 OPERATION
3.1 GENERAL
The generating set is operational after full installation and
filling up with: fuel, engine lubricating oil and cooling liquid,
connecting the battery to earth and connecting the digital
remote control panel.
Fig. 17:
3.2 OPERATING INSTRUCTIONS
3.2.1 Summarised operating instructions (daily
use)
Routine "pre-start" checks:
1 Check oil level (refer to fig. 17).
2 Check cooling system (coolant level).
3 Power source selector switch (off/external
power/generator power). Switch to power source
switch "OFF", or switch off all consumers in the usual
way. If a Mass Systemswitch is installed, this operates
automatically.
4 Switch on battery switch (when installed).
5 Fuel valve: open.
Starting:
Push the start button to initiate the full automatic
starting procedure. You can monitor the procedure on
the display.
In operation checks:
1 Check for abnormal noise or vibration
2 Check the voltage
3 Power source selector switch (off/external
power/generator power). Switch to power source
generator. If a Mass Systemswitch is installed, this
operates automatically.
4 Before loading the generating set up to maximum,
have it run warm. Continuous load should be
restricted to 70 % of maximum load.
Stopping generator:
1 Switch off all electrical devices (consumers). If the
generating set has been running under full load for a
longer period, do not shut it down abruptly. Reduce
the electrical load to about 30% of the rated load and
let it run for approx. 5 minutes.
2 Press the STOP button.
3 Switch to an other AC power source, if available. If a
Mass Systemswitch is installed, this is done
automatically.
3.2.2 Extended operating instructions
Check when starting the first time or after a longer period
of rest:
1 If there is any damage caused by transport or
installation.
2 Check if the installation conforms to the installation
instructions.
3 Ensure the generating set is free to turn without
obstruction.
4 Check all hoses and hose connections for leaks.
5 Check all cables and cable end terminal connections.
6 Check the engine and generator mounting bolts.
Routine "pre-start" checks:
1 Check engine oil level.
The generator switches off in the event of insufficient
oil-pressure. Even when the oil level is too low the oil
pressure can be high enough. Do not run the
generator with the oil below the lowest mark in the,
because a smaller volume of oil will become
contaminated considerably quicker than a larger
volume. Therefore we recommend daily oil-checks.
Check oil level prior to starting the engine or at least 5
minutes after the engine has stopped.
1
2
1 Maximum oil level
2 Minimum oil level

Table of Contents

Other manuals for Mastervolt WHISPER 12 ULTRA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mastervolt WHISPER 12 ULTRA and is the answer not in the manual?

Mastervolt WHISPER 12 ULTRA Specifications

General IconGeneral
BrandMastervolt
ModelWHISPER 12 ULTRA
CategoryInverter
LanguageEnglish

Related product manuals