TROUBLE SHOOTING
EN / WHISPER 12 Ultra - Three phase for mobile applications / December 2008 / Copyright © 2008 Mastervolt 35
PROBLEM CAUSE SOLUTION
Poor fuel quality.
Use better quality diesel.
Poor quality lubricating oil.
Use better quality oil.
Continuous running with very low load.
Increase load up to 70% of nominal power and
have the engine run for a few hours
Wrong measurement. Check if the load is measured correctly. Does the Amp meter show
the correct value? When calculating the load by multiplying voltage and amps this should be
done by using the exact values, taking into account the power factor of the consumers. When
any doubt, measure the power directly with an appropriate instrument.
Overfull oil sump.
Bring the oil to the correct level
Choked fuel filter.
Replace the fuel filter.
Choked air filter element.
Check air inlet openings; clean or replace air filter
element.
Exhaust blocked.
Check the exhaust system.
Faulty fuel pump
Check and replace if nescessary
Injector blocked.
Have the injector checked.
Loss of compression, sticking or
damaged piston ring.
Have the compression measured.
Clean or replace the rings.
Loss of power
Wear out of cylinder.
Have the compression measured and have the
engine overhauled.
Overload.
Take away the overload.
Low level of coolant or air in the
cooling system
Fill up with coolant and release air bubbles.
Check if there are air blocks in the system; refer
to the installation manual
Broken impeller.
Radiator choked by dirt
Hot air circulation in radiator.
Check the cooling system thoroughly.
Clean radiator
Broken or slipping V-belt.
Replace and adjust the V-belt tension.
Over-temperature
Faulty thermostat
Check the thermostat or replace.
5.2.3 Warnings
Generator must be shut off immediately if:
Motor RPM suddenly rises or drops.
Unusual noise comes from generating set.
Exhaust gases suddenly colour dark.
Engine failure warning light is on
5.2.4 Service address
If you cannot correct a problem with the aid of the mal-
function table, contact your Mastervolt Service Centre or
Mastervolt Amsterdam for an extended service list, tel: INT
+31-20-3422100.

Table of Contents

Other manuals for Mastervolt WHISPER 12 ULTRA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mastervolt WHISPER 12 ULTRA and is the answer not in the manual?

Mastervolt WHISPER 12 ULTRA Specifications

General IconGeneral
BrandMastervolt
ModelWHISPER 12 ULTRA
CategoryInverter
LanguageEnglish

Related product manuals