SUMMER/WINTER MODE CHANGE
I/O resource - Parameter Value
ID2 can be acvated via H46 3
Open contact -> heat pump in cooling mode.
Closed contact -> heat pump in heang mode.
DHW CALL FROM DIGITAL INPUT
I/O resource - Parameter Value
ID9 can be acvted via H53 28
Closed contact -> acve DHW call.
Open contact -> inacve DHW call.
SYSTEM WATER REMOTE PROBE
I/O resource- Parameter Value
ST7 can be acvated via H18 41 Enables plant remote probe
heang
Temperature detected by the heat pump delivery probe < Hea setpoint -
and
Temperature detected by system remote probe < Hea water setpoint - b22
cooling
Temperature detected by the heat pump delivery probe > Coo setpoint+
and
Temperature detected by system remote probe > Coo setpoint + b22
Nota
AUXILIARY HEATERS
Parameter r24
- r24=0
- r24=1
- r24=2
- r24=3
PLANT HEATER
r12
r29 or r30).
water setpoint minus r11
I/O resource - Parametro Value
r10 1 Funcon enabling