31
i-32V5
Parame-
ter
 Unit   

 Notes
Coo First cooling setpoint °C 7.0 25÷Coo2 U
Hea First heang setpoint °C 45.0 Hea2÷H01 U
San Sanitary setpoint °C 48.0 25÷H01 U
If sanitary funcon
acve. See par. 10.2
Coo2 Second cooling setpoint °C 18.0 Coo÷25 U
Hea2 Second heang setpoint °C 35.0 25÷Hea U
*rCO
Mixing valve summer set-
point
°C 15.0 -50÷80 I
Cong if Gi accessory
present
*rHE Mixing valve winter setpoint °C 30.0 -50÷80 I
Cong if Gi accessory
present
H10 Sanitary funcon enabling / 0 0÷6 I See par. 10.2
H17
Input conguraon
Analogue ST6
/ 0 0÷49 I
0 = Input disabled
6 = Domesc hot water probe
H18
Input conguraon
Analogue ST7
/ 0 0÷49 I
0 = Input disabled
41 = Remote water temperature
probe
H22
0-10vDC live input congu-
raon
Analogue ST11
/ 0 0÷49 I
0 = Input disabled
40 = Plant setpoint decalibraon
*H27
Input conguraon
Analogue ST5E
/ 0 0÷49 I
0 = Input disabled
44 = Mixer probe
Only if Gi accessory
present
*H28
Input conguraon
Analogue ST6E
/ 0 0÷49 I
0 = Input disabled
39 = Solar storage tank probe
Only if Gi accessory
present
*H29
Input conguraon
Analogue ST7E
/ 0 0÷49 I
0 = Input disabled
38 = Solar collector probe
Only if Gi accessory
present
H46
Input conguraon
Digital ID2
/ 0 0÷30 I
0 = Input disabled
3 = Summer/winter mode change
H47
Input conguraon
Digital ID3
/ 2 0÷30 I
0 = Input disabled
2 = Remote On / O
H52
Input conguraon
Digital ID8
/ 0 0÷30 I
0 = Input disabled
28 = DHW thermostat call
H53
Input conguraon Digital
ID9
/ 0 0÷30 I
0 = Input disabled
21= Hz min/max remote
25= Silenced version
26 = Double set-point call
*H63
Input conguraon
Digital ID9E
/ 0 0÷30 I
0 = Input disabled
19 = room thermostat
Only if Gi accessory
present
H75 Digital inputs polarity / 0 0÷255 I
0 = Digital inputs N.A.
1 = ID1 polarity inverted
2 = ID2 polarity inverted
4 = ID3 polarity inverted
8 = ID4 polarity inverted
16 = ID5 polarity inverted
32 = ID6 polarity inverted
64 = ID7 polarity inverted
128 = ID8 polarity inverted
H76 Digital inputs polarity / 0 0÷255 I
0 = Digital inputs N.A.
1 = ID9 polarity inverted
2 = ID10 polarity inverted
4 = ID1E1 polarity inverted
8 = ID2E1 polarity inverted
16 = ID3E1 polarity inverted
32 = ID4E1 polarity inverted
64 = ID5E1 polarity inverted
128 = ID6E1 polarity inverted
H77 Digital inputs polarity / 0 0÷255 I
0 = Digital inputs N.A.
1 = ID7E1 polarity inverted
2 = ID8E1 polarity inverted
4 = ID9E1 polarity inverted
8 = ID10E1 polarity inverted
16 = ID1E2 polarity inverted
32 = ID2E2 polarity inverted
64 = ID3E2 polarity inverted
128 = ID4E2 polarity inverted
H81
Output conguraon
In DO3 power
/ 22 0÷47 I
0 = Output disabled
22 = Plant integraon heater
26 = DHW integraon heater
H84
Output conguraon
In DO6 power
/ 6 0÷47 I
0 = Output disabled
6 = DHW valve
H85
Output conguraon
In DO7 power
/ 25 0÷47 l
0 = Output disabled
25 = Double set-point valve
29 = Boiler enabling
24 = Alarm warning
31 = Summer/winter operang
mode warning
21 = Defrost warning
47 = Machine block warning