i-32V5 Air/water inverter heat pumps with axial fansi
27
The power cables, electrical protecons and line fuses must be sized in accordance with what is reported in the unit's wiring diagram and in the
electrical data contained in the technical characteriscs table
Use a dedicated power line, do not power the appliance through a line to which other users are connected. Fasten the power cables securely and
make sure they do not come into contact with sharp corners. Use double insulated cables with copper wires.
The ground connecon must be carried out rst during the connecon phase, vice versa it must be removed last when the unit is disconnected.
In the event of any loosening of the power cable, it must be ensured that the tension of the acve conductors takes place before that of the
ground wire.
A main switch or a disconnecon device with adequate breaking capacity must be installed on the power supply line, which has a separaon of
the contacts in all the poles. The dierenal protecon switch must be compable with inverter appliances, it is recommended to install a type
B dierenal switch, the installaon of a dierent type switch could give rise to unmely trips.
The following table shows the recommended cable secons for a maximum length of 30 m. In any case, depending on type of installaon, the
locaon and the length of the cables (be it less than or greater than 30m), the electrical system designer will make an appropriate choice.
Model
230V / 1ph i-32V504 3 x 2,5 mm2 L/N: 3,4 Nm – PE: 1 Nm
230V / 1ph
i-32V506 / i-32V508,
SL08
3 x 4 mm2 L/N: 3,4 Nm – PE: 1 Nm
230V / 1ph
i-32V510 / i-32V512,
SL12
3 x 4 mm2 L/N: 3,4 Nm – PE: 1 Nm
230V / 1ph
i-32V514 / i-32V516,
SL16
3 x 6 mm2 L/N: 3,4 Nm – PE: 1 Nm
400V / 3ph
i-32V510T / i-32V512T,
SL12T
5 x 2,5 mm2 L1/L2/L3: 3,4 Nm – N/PE: 1 Nm
400V / 3ph
i-32V514T / i-32V516T,
SL16T
5 x 2,5 mm2 L1/L2/L3: 3,4 Nm – N/PE: 1 Nm
400V / 3ph i-32V518T 5 x 4 mm2 L1/L2/L3: 3,4 Nm – N/PE: 1 Nm
The units comply with the electromagnec compability specicaons, however the designer of the electrical system must full appropriate
assessments to ensure the absence of interference.
The connecon terminal block is located under the machine cover. The terminal block must be connected respecng the notes below. The con-
necons shown below are standard. Other connecons are given in the MCO manual of the on-machine control of the i-32V5 (see "USER AND
INSTALLER CONFIGURATION TABLES"), according to the conguraons adopted.
TERMINAL CONNECTION TYPE
X-1 Connect the ground cable
Inlet for power supply 1-Ph/N/PE,230V, 50Hz
(only for sizes 06/08, SL08/10/12,SL12/14/16,
SL16
N Connect the neutral cable from the mains
L Connect the phase cable from the mains
PE Connect the earth cable
Input for power supply 3-Ph/N/PE, 400 Vac,
50Hz.
(only for size 10T,12T,14T,16T,18T, SL12T,16T)
N Connect the neutral cable from the mains
L1 Connect the phase cable L1 from the mains
L2 Connect the phase cable L2 from the mains
L3 Connect the phase cable L3 from the mains
X-5.2 Connecon of modbus RTU signal + for remote keyboard
Modbus communicaon
X-5.1 Connecon of modbus RTU signal – for remote keyboard
X-4.1
Connecon of modbus RTU earth reference for remote
keyboard (GND)
X-12.1 Remote keyboard power supply (12V, 50Hz, 500mA)
Outpu for power supply 12Vac, 50Hz
X-12.2 Remote keyboard power supply (12V, 50Hz, 500mA)
X-17.1/X-17.2 DHW probe (SAN1) Analogue or digital input
X-19.1/19.2 Plant remote probe (IMP1) Analogue input
X-20.1/X-20.2 Double set point (Q4) Analogue input
X-22.2 0-10V (+) signal input to modify set point
Analog input (ST10)
X-22.1 0-10V (-) signal input to modify set point
X-6.1/X-6.2 Plant heater (Rimp)
Output in single phase voltage 230Vac, 50Hz,
5A resisve, 1A inducve.
Can be used in versions without KA
X-9.1/X-9.2 Exchanger heater (R2)
Output in single phase voltage 230Vac, 50Hz,
5A resisve, 1A inducve.
Can be used in versions without KA
X-10.1/X-10.2 Base heater (R3)
Output in single phase voltage 230Vac, 50Hz,
5A resisve, 1A inducve.
X-11.1/X-11.2 Domesc hot water valve outlet (VS1)
Changeover contact, single phase voltage
230Vac, 50Hz, 5A resisve, 1A inducve.