i-32V5 Air/Water heat pumps wih axial fans
42

(1) Cooling: outdoor air temperature 35°C; in/out water temperature 12/7°C.
(2) Cooling: outdoor air temperature 35°C; in/out water temperature 23/18°C.
(3) Heang: outdoor air temperature 7°C db 6°C db; in/out water temp 30/35°C.
(4) Heang: outdoor air temperature 7°C db 6°C db; in/out water temp 40/45°C.
(5) Cooling: in/out water temperature 7/12°C.
(6) Heang: average climac condions; Tbiv=-7°C; in/out water temp 30/35°C.
(7) Indicave data subject to changes. For the correct value, always refer to the technical label on the unit.
UNIT AND AUXILIARY ELECTRICAL DATA
Unit power supply V/~/Hz 400/3PH+PE/50
On board controller circuit V/~/Hz 12/1/50
Remote controller circuit V/~/Hz 12/1/50
Fans power supply V/~/Hz 400/3PH+PE/50
For sizes 04, 06, 08, SL08, 10, 12, SL12 14 e 16, SL16* - For sizes 10T, 12T, SL12T, 14T, 16T, SL16T e 18T**


12. OPERATING LIMITS
EVAPORATOR WATER FLOW RATE
The nominal water ow rate refers to a 5°C temperature dierence between the evaporator inlet and outlet. The maximum permied ow rate
features a 3°C temperature dierence while the minimum one has an 8°C temperature dierence at the nominal condions as shown in the
technical sheet.



For greater details, we have aached a table below with the minimum ow rates for the plate heat exchanger to guarantee proper operaon
according to the model (please note: the water ow switch is applied to protect against failed triggering of the anfreeze probe due to the lack
of ow but does not guarantee the minimum water ow rate required for correct operaon of the unit).
Model
i-32V5
04 06  10 10T

SL12

SL12T
14 14T

SL16

SL16T

Minimum water ow to be assured in
chiller mode (condion (1) technical
sheet) [l/s]
0,13 0,15 0,17 0,23 0,25 0,34 0,34 0,41
Maximum water ow to be assured in
chiller mode (condion (1) technical
sheet) [l/s]
0,34 0,40 0,46 0,60 0,68 0,92 0,92 1,10
[l/s] Minimum ow switch water ow
rate* [l/s]
0,117 0,117 0,117 0,153 0,153 0,153 0,262 0,262
Maximum ow switch water ow
rate* [l/s]
0,132 0,132 0,132 0,175 0,175 0,175 0,293 0,293
* When the ow rate drops below the indicated limit (ow switch minimum water ow rate) the ow switch issues an alarm, which may be reset
only upon reaching the maximum indicated ow rate.

The minimum permissible temperature at the evaporator outlet is 5°C. For lower temperatures, contact our technical department. In this case,
contact our technical department for a feasibility study and evaluaon of the modicaons to be made according to the requirements. The
maximum temperature that can be maintained at steady state at the evaporator outlet is 25°C.

When the system has reached steady state, the water inlet temperature must not drop below 25°C: lower values, not due to transient phases
or reaching steady-state, can cause system failures and could possibly break the compressor. The maximum outlet water temperature must not
exceed 60°C.
There could be failures to the regular operaon of the unit or, in more crical cases, the safety devices could be triggered due to temperatures
higher than those indicated, especially if coupled with reduced water ow rates.
AMBIENT AIR TEMPERATURE AND SUMMERISED TABLE
The units are designed and built to operate in summer mode, with condensaon control, at outdoor air temperatures between -10°C and +46°C.
In heat pump mode, the allowed temperature range of the outdoor air is from -19°C to 39°C depending on the outlet water temperature as
shown in the table below.
