i-32V5 Air/water inverter heat pumps with axial fansi
43

Room temperature Minimum -10°C Maximum +46°C
Outlet water temperature Minimum +5°C Maximum +25°C
Heat pump mode
Room temperature Minimum -20 °C Maximum +30°C
Outlet water temperature Minimum +25 °C Maximum +60 °C

Room temperature with water at maximum 39°C Minimum -20 °C Maximum +40 °C
Room temperature with water at maximum 55°C Minimum -10 °C Maximum +35 °C
Outlet water temperature Minimum +25 °C Maximum +60 °C
The following are the graphical operang limits for heang, air condioning and domesc hot water producon.
HEAT PUMP MODE
20
25
30
35
40
45
50
55
60
65
0,0
10,0
20,0
30,0
40,0
Tw [
°
C]
Ta [
°
C]
i-32V5 Heating
COOLING MODE
0
5
10
15
20
25
30
-20,0
-10,0
0,0
10,0
20,0
30,0
40,0
50,0
Tw [
°
C]
Ta [
°
C]
i-32V5 Cooling