7.3.4 INVERTER COMPRESSORS CONTROL IN COOLING MODE
The management of the compressors depends on the ambient temperature and on the water temperature setpoint.
The PI type regulation with:
ST = regulation temperature sensor
Set cool (G01) = setting of cooling setpoint
b01 = cooling regulator proportional band
b05 = compressor control delta cut-off
b25 = compressor regulation delta cut-on
b07 = integral time
HzMin = Minimum frequency of operation derived from the algorithms of limitation
HzMaxReg = Maximum working frequency of the compressor in cooling mode based on the limitations described in the
previous paragraphs
466
475
485
695
6105
6115
b05 (°C)
0,5
0,5
0,5
0,5
0,5
0,5
b25 (°C)
2,5
2,5
2,5
2,0
2,0
2,0
7.3.5 INVERTER COMPRESSORS CONTROL IN HEATING MODE
The compressors are active in heating mode if the heat pump is enabled
H09 = Configuration of the heat pump presence parameter (0 = Heat pump not present; 1 = heat pump is present)
ST = regulation temperature sensor
Set heat G02= setting of heating setpoint
b02 = compressor regulation band in heat pump mode
b05 = compressor control delta cut-off
b25 = compressor regulation delta cut-on
b07 = integral time
HzMin = Minimum frequency of operation derived from the algorithms of limitation
HzMaxReg = Maximum working frequency of the compressor in cooling mode based on the limitations described in the
previous paragraphs.
For the values of the parameters b05 and b25, please refer to the table reported in the previous paragraph.
The following curve shows the adjustment without integral component (b07 = 0)