37
Position gate half-way open and STOP gate.
This gate position will put the most amount of
resistance on the ERD sensor when gate cycles.
This operator is equipped with an ERD Sensor - Electronic Reversing Device (Type A) that functions as entrapment protection
according to UL 325 standards. The gate will reverse direction after encountering an obstruction in either the OPEN or
CLOSE gate cycle.
When the gate encounters an obstruction during the CLOSE cycle, it will reverse to the open position and PAUSE the gate. An
input command (press remote button or exit loop) is needed BEFORE the gate will reset and close again.
When the gate encounters an obstruction during the OPEN cycle, it will reverse approximately 6 inches and PAUSE the gate. An
input command (press remote button or exit loop) is needed BEFORE the gate will reset and open again.
For the ERD Sensitivity to function correctly:
• THE RELEASE HANDLE CLAMP MUST NOT SLIP when the gate encounters an obstruction.
• Limit switches must be learned BEFORE adjusting the ERD Sensitivity.
Adjustments
reverse sensor (erd)
STOP Gate
Half-way
CLOSE gate. If ERD sensor triggers, reduce
sensitivity. If sensor does NOT trigger,
sensitivity is set correctly.
CLOSE Gate
1
2
A. Turn knob until blue LED lights up.
Max sensitivity reached, Position 1.
“1” - Maximum sensitivity setting.
Too sensitive for most gates. (LED lights)
“16” - Minimum sensitivity setting.
Not sensitive enough for most gates. (LED is off)
B. Turn knob counter-clockwise to reduce
sensitivity during ERD testing as needed.
(LED remains OFF for all but position 1)
IMPORTANT: When satisfied with ERD adjustment,
cycle the gate 3 or 4 times to make sure that the ERD
sensor does not falsely trigger during normal gate
operation. Readjust if this happens.
When solid gates are installed in:
• Unusually high wind areas
• Uphill opening gate
• Heavy gate
ERD sensor can be set to Min (position 16)
to keep the gate cycling normally in such
extreme conditions.
CAUTION: Minimum sensitivity setting
(position 16) results in gate exerting
MAXIMUM force before reversing direction.
Testing ERD Sensitivity
“Min” ERD Position 16 Setting
Adjusting ERD Sensitivity
TIP: While Adjusting ERD. . . . .
16 sensitivity setting positions.
NO mechanical hard stop for knob.
PhotoCell
Edge
UL Entrap
1
2
Limit SW
ON-LINE
MATRIX
JOG
LEFT
JOG
RIGHT
Jog LT
Jog RT
GND
Edge 1
Edge 2
Photo
Cell
ERD
Motor
OverLoad
POWER
MC-200
Motor Controller
16
15
14
13
12
3
4
5
MAX
LED ON
Edge
Sensitivity
ERD
16
15
14
13
12
3
4
5
MAX
LED ON
Sensitivity
ERD
16
15
14
13
12
3
4
5
MAX
LED ON
Sensitivity
ERD
External Alarm
Reset Button
OPEN STOP CLOSE
MOTOR MOTION
Matrix 1
PRE
SS
to RESE
T
Allow the gate to strike an immobile object while OPENING and
CLOSING. The gate MUST reverse direction after striking the object.
Increase or decrease the ERD Sensitivity as needed. Repeat this
process until the correct sensitivity is achieved. If alarm sounds
while preforming this procedure,
press STOP BUTTON on Matrix 1
or externally mounted Alarm
Reset button to shut-off alarm.