EasyManua.ls Logo

McQuay M5WM Series User Manual

McQuay M5WM Series
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background image
Page 10 IM-5WMF(SEER13)-0706
Refrigerant Tubing
Tubing Length & Elevation
Copper tubing to connect the indoor and outdoor units is
supplied by others or it can be ordered from the factory.
See Table 1 for requirements. Cover both tubes individually
with 3/8” wall foam insulation.
Table 1. Refrigeration Tubing Requirements
Model 10 15 20 25
Maximum length, ft., L
40 40 50 50
Max. elevation, ft., H
16 16 26 26
Max. number of bends
10 10 10 10
Liquid tube size – OD
¼” ¼” ¼” ¼
Gas tube size - OD
3/8” ½” ½” 5/8”
Note: The refrigerant pre-charged in the outdoor unit is for tubing length up
to 25ft. See Table 5, page 18 for additional R410A refrigerant required on
longer runs.
Figure 10. Tubing Length and Elevation
Tubing Preparation
Do not use contaminated or damaged copper tubing. Do
not remove plastic, rubber plugs and brass nuts from the
valves, fittings, tubings and coils until you are ready to
connect suction or liquid line into valves or fittings.
If any brazing work is required, ensure that the nitrogen
gas is passed through coil and joints while the brazing
work is done. This will eliminate soot formation on the
inside wall of the copper tubing.
Cut the copper tubing with a tube cutter. See Figure 11.
Remove burrs from cut ends by holding tubing
downwards to prevent metal chips from entering the
tubing.
Slide the flare nuts, for both the indoor unit and outdoor
unit onto the copper tubing.
Flare the tubing as shown in Figure 11, Figure 12 and
Table 2.
The flare must be even and not cracked or scratched.
Figure 11. Cutting and Flaring Tube
Table 2: Tube Flaring Dimensions
Tube Diameter - OD X (in.)
Inch Imperial Rigid
¼ .051 .028
3/8 .063 .039
½ .075 .051
5/8 .087 .067
Tubing Connection To Units
Connect the copper tubing to both the indoor and
outdoor units. See Figure 12.
Torque each flare nut to specifications. See Table 3.
Cover both tubes individually with 3/8” minimum wall
foam insulation.
Table: Flare Nut Torque Specifications
Tube Size (in.) Torque (ft./lb.)
¼ 13.3
3/8 31.0
½ 40.6
5/8 48.0
Figure 12. Flare Tubing Connections
H L
Outdoor Unit

Questions and Answers:

McQuay M5WM Series Specifications

General IconGeneral
BrandMcQuay
ModelM5WM Series
CategoryAir Conditioner
LanguageEnglish

Summary

Safety Precautions

Warnings and Cautions

Essential safety warnings and cautions for installation and operation.

Installation Guidelines

Piping Installation

Refrigerant Tubing

Tubing Preparation and Connection

Steps for preparing copper tubing and making flare connections with torque specifications.

Electrical Connections

Wire and Breaker Requirements

Details on wire gauge, number of wires, and fuse/breaker sizes for unit connections.

Cooling Only Wiring

Wiring diagrams for cooling-only units, showing terminal block connections.

Heat Pump Unit Wiring

Wiring diagrams for heat pump units, detailing connections for 10 & 15 size.

Cooling Only Wiring (Sizes 20 & 25)

Heat Pump Unit Wiring (Sizes 20 & 25)

Wiring diagrams for heat pump units, detailing connections for 20 & 25 size.

Wiring Diagrams

Vacuuming and Charging

Purging Piping and Indoor Unit

Procedure for removing air and moisture from refrigerant lines before charging.

Charge Operation

Steps for adding refrigerant to the unit using a gas cylinder and weighing machine.

Special Precautions for R410A

Remote Controller Operation Guide

Service and Maintenance

Troubleshooting Guide

Common problems and their potential causes and treatments for unit malfunctions.

Related product manuals