Technical Data
Correction Factors With Glycol Use
GLYCOL % COOLING CAPACITY WATER FLOW PRESSURE DROP
10 0.990 1.015 1.06
20 0.980 1.040 1.12
30 0.970 1.080 1.18
40 0.965 1.135 1.24
Water Pressure Drop And Flow Rate
Water Flow Rate Water Pressure Drop
MODEL
L/s m³/h kPa Bar
MAC080C
1.08 3.9 74 0.74
MAC100C
1.31 4.7 82 0.82
MAC120C
1.67 6.0 76 0.76
MAC150C
2.0 7.2 74 0.74
Cooling
1.08 3.9 74 0.74
MAC080CR
Heating
1.14 4.1 72 0.72
Cooling
1.31 4.7 82 0.82
MAC100CR
Heating
1.39 5.0 80 0.80
Cooling
1.67 6.0 76 0.76
MAC120CR
Heating
1.78 6.4 74 0.74
Cooling
2.0 7.2 75 0.45
MAC150CR
Heating
2.11 7.6 73 0.73
Page 20