EasyManua.ls Logo

McQuay MCW 200 C - Page 38

McQuay MCW 200 C
41 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Valve Actuator installation
Latch the manual operating lever in the engaged position (N.C. only).
Depress the release button (See Figure 19). Align the body with the actuator to ensure the stem is inserted
into the large mating hole on the bottom side of the actuator. Engage the actuator on the body and release
the button. Actuator AG2 is used or normally open operation. Actuator AG1 is used for normally closed
operation.
Mounting
The PopTop
TM
valve can be mounted vertically or horizontally. If mounted horizontally, the valve should be
mounted within 90°of upright position (See Figure 20). If mounted vertically, care should be taken to ensure
moisture does not drip onto motor. The valve actuator should not be mounted upside down.
Figure 19
Figure 19 Figure 20
Room Thermostats
The RAB10… room thermostat is used in heating or cooling systems to maintain the selected room
temperature.
Functions
Heating If the room temperature falls below the selected set point, the heating contact will close.
Release
Button
Manual
Operating
Lever
Stem
Mating Hole
Vertical
Upside Down
B
°
A
Cooling If the room temperature exceeds the selected set point, the cooling contact will close.
Fan speed There are two possibilities to control the fan speed:
a) Manually by means of the three-speed fan switch on the thermostat for continuous
operation.
b) Automatically by switching to the selected fan speed via the thermostat for controlled
operation. In that case - prior to commissioning - the thermostat function must be
changed. There are two choices available:
Auto
Selected fan speed as continuous operation
Fan is switched at the same time as the valve
Page 37

Related product manuals