DC8xD MK3 GENSET CONTROLLER USER MANUAL
29
Pressure/Temper
ature unit
℃/KPA
℃
/BAR
℃/PSI
F/KPA
F/BAR
F/PSI
Crank times under mode and test
mode.
Crank times under auto mode.
RPM
Hz
Oil pressure(delay)
RPM/Frequency
RPM/Oil Pressure
Frequency/Oil Pressure
RPM/Frequency/Oil press.
1.If there is no oil pressure sensor,
please dont choose the type.
2. The oil pressure switch input does
not participate in the oil pressure
return motor.
3. The operating status of the unit, the
success condition of the shutdown are
consistent with the successful
conditions of the start, and the
corresponding judgment is made.
4. "/" represents the relationship or the
condition that any condition is satisfied
when the motor is retracted. However,
successful parking requires several
conditions to be met at the same time.
Rated RPM multiplying by this value is
regarded as crank success condition.
When the RPM is over the condition
value, then system regards it as crank
success, motor escaped.
Rated frequency multiplying by this
value is regarded as crank success
condition. When the gens frequency is
over the condition value, then system
regards it as crank success.
When the engine oil pressure is over
the condition value, then system
regards it as crank success, motor
escaped.
When the fuel level is lower than
preset value and remains 10S, fuel
pump opened signal output
When the fuel level is higher than
preset value and remains 1S, fuel
pump closed signal output.
When it is set as 5000, then this
function is disabled.
When it is set as 2000/01/01, this