DC8xD MK3 GENSET CONTROLLER USER MANUAL
32
the value is set as 200, then the high temperature alarm
is disabled.
When the fuel level is lower than the value and comes
into low fuel level warning delay but still lower (normal
warning delay), then low fuel level warns. If it is higher
than the value then warning clears. If the value is set as
0, then the low fuel level warning is disabled.
Under battery
voltage warning
Rated battery voltage multiplying by this value is
regarded as under battery voltage warn value. when the
battery input is lower than the warning value and comes
into under battery voltage delay but still lower (normal
faults delay), then under battery voltage warns. if the
value is set as 0, then under battery voltage is disabled.
Rated frequency multiplying by this value is regarded as
under over frequency alarm value. When the Freq is
higher than the value and comes into over freq delay
but still higher (emergency faults delay), then over
frequency alarms. If the value is set as 200, then the
alarm is disabled.
Rated frequency multiplying by this value is regarded as
under frequency alarm value. When the Freq is lower
than the value and comes into under freq delay but still
lower (normal faults delay), then under frequency
alarms. If the value is set as 0, then the alarm is
disabled.
Rated voltage multiplying by this value is regarded as
over voltage alarm value. When the voltage is higher
than the value and comes into over voltage delay but
still higher (normal faults delay), then over voltage
alarms. If the value is set as 200, then the alarm is
disabled.
Phase current
over-load alarm
Rated current multiplying by this value is regarded as
over current alarm value. When the current is higher
than the value and comes into over current delay but
still higher (over current faults delay), then over current
alarms. If the value is set as 200, then the alarm is
disabled.
Rated voltage multiplying by this value is regarded as
under voltage alarm value. When the voltage is lower
than the value and comes into under voltage delay but
still lower (normal faults delay), then under voltage
alarms. If the value is set as 0, then the alarm is
disabled.
Rated power multiplying by this value is regarded as
over power warn value. When the loading power is
higher than the value and comes into delay but still
higher (normal warn delay), then over power warns. If
the value is set as 200, then the warning is disabled.
4)Output/input setting