MFT1700/1800 Series
Multifunction Tester
Quick Start Guide
GSAFETY WARNINGS
n Safety warnings and precautions must be read and understood before
the instrument is used. They must be observed during use.
n The circuit under test must be switched off, de-energised and isolated
before test connections are made when carrying out insulation and
continuity tests.
n Continuity of protective conductors and earthed equipotential bonding
of new or modified installations must be verified before carrying out an
earth fault loop impedance test, RCD or earth testing
n Do not touch circuit connections and exposed metalwork of an
installation or equipment under test. Under fault conditions the system
earth could become hazardous live.
n Do not touch the earth stakes, test leads and their terminations
(including connections to the earthing system under test) if an
installation earth fault can arise unless adequate precautions are taken.
n The ‘live circuit warning’ and ‘Automatic discharge’ functions are
additional safety features and should not be regarded as a substitute
for normal safe working practices.
n Do not move the rotary switch positions while a test is in progress.
n Do not operate the instrument or connect it to any external system
if it shows any visible signs of damage or if it has been stored for
prolonged periods in unfavourable conditions.
n Do not operate the instrument or connect it to any external system
if the battery compartment or casing is open or any parts of the case
(including keypad, selector switch, display window, etc.) are missing.
n Always disconnect the instrument from all systems while batteries are
being changed or the fuse replaced
n Do not replace the rechargeable cells in the MFT1730 and 1835 with
non-rechargeable “dry” cells and attempt to charge the cells. This can
cause explosion or fire.
n Do not operate the charging equipment supplied with the MFT1730 or
MFT1835 in damp or wet environments or outside. All test leads must
be removed from the instrument while charging.
n After insulation tests, capacitive circuits must be allowed to discharge
before disconnecting test leads. Locking the Insulation test ON should
only be used where there is no risk of a circuit holding a charge.
All manuals and user guides at all-guides.com
all-guides.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Megger MFT1710 and is the answer not in the manual?

Megger MFT1710 Specifications

General IconGeneral
BrandMegger
ModelMFT1710
CategoryTest Equipment
LanguageEnglish

Related product manuals