10
Environmental
Operating temperature:
-10°C to 50°C
Storage temperature:
-25°C to 65°C
Ingress protection (lid closed):
IP65
Humidity:
90% RH non-condensing at 40°C
Dimensions:
305 x 194 x 360 (mm) (12 x 7.6 x 14.2 inches)
Weight:
6.75 kg (15lb) approx
Voltage output accuracy (0°C to 30°C):
0 - +4% of nominal test voltage at 100 M load
Current measurement range:
±0.01 nA to ±5 mA
Current measurement accuracy (23°C):
±5% ±0.2 nA at all voltages
Display:
Analogue/Digital 3 digits
Interference rejection:
2mA rms
Timer range:
Counts up to 99 minutes from start of test
Test regimes
Auto IR
Lead set:
Three flexible silicon insulated leads with compact clamp.
Safety:
Meets the requirements of EN61010-1:2001 CAT III 300V
EMC:
Meets the requirements of EN61326-1:1998 for use in heavy industrial areas.

Other manuals for Megger MIT510

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Megger MIT510 and is the answer not in the manual?

Megger MIT510 Specifications

General IconGeneral
BrandMegger
ModelMIT510
CategoryTest Equipment
LanguageEnglish