Recommended environment: 20° to 25° C (68° to 77° F.); 50% relative humidity;
computer room or other temperature- and humidity-
controlled environment
Operating temperature: 0° to 40° C (32° to 104° F.) except battery
Storage: -20° to 50° C (-4° to 122° F.)
Humidity: up to 90% non-condensing (operating)
Altitude: sea level to 1,000 meters (sea level to 3,280 feet)
without derating; 1,000 to 2,000 meters (3,280
to 6,560 feet): derate operating temperature to a
maximum of 28° C (82° F)
Acoustic noise:
AC input ratings
Voltage: 480 VAC, ± 15%
Frequency: 60 Hz, ± 10%
Phases: 3 Ø (phase sequence must be A, B, C)
Wires: 3 or 4 wires plus ground
Current: 2,000 Amperes
AC output ratings
Voltage: 480 VAC
Frequency: 60 Hz
Phases: 3 Ø
Wires: 4 wires plus ground
Current: 2,000 Amperes
Power factor: 0.8 lagging
1.6.1 Electrical
1.6 Specifications,
Static Switch
Cabinet
AVknignitar051522003573005057
detartaesioncitsuoccA
teef5taABdnidaol
fotnorfehtmorf
eludomSPUeht272727275787
1.5.3 Environmental
1 — 15Introduction
User’s guide