How to remove the electrical 
parts.  
1)  Perform work of item 1,2. 
2)  Remove the four screws 
fixing the IPM board.  
3)  Unfasten the connector 
of the reactor. 
4)  Unfasten the connector 
of the compressor. 
5)  Disconnect following 3 
pieces of connection wires and 
connectors between IPM and 
PCB.  
 
 
CN1(5p,white) 
CN14(3p,white) 
CN3(red or brown)   
CN5(blue) 
 
 
 
6)  Remove the IPM board.