64 
 
7.4.2.4 E4 (Outdoor temperature sensor (coil sensor T3,ambient sensor T4, Compressor discharge 
sensor T5、indoor coil outlet pipe sensor T2B) malfunction) diagnosis and solution 
F1/F2/F3/F4/F5 (No.A,B,C,D,E Indoor unit coil outlet temp. sensor malfunction) diagnosis and 
solution. 
. 
If the sampling voltage is lower than 0.06V or higher than 
4.94V, the LED will display the failure.  
●  Wiring mistake 
●  Faulty sensor  
●  Faulty PCB  
Trouble shooting: 
Check the connections 
between temperature 
sensor and PCB. Are 
the connections good?
Correct the connections.No
Yes
Yes Replace indoor or outdoor PCB.
Replace the sensor 
Check the resistance value 
of the sensor via Appendix 1 
and Appendix 2
Is it normal?
No