11 
 
4.  Installation Details 
4.1 Wrench torque sheet for installation 
Additional tightening torque 
 
4.2 Connecting the cables 
The power cord connection should be 
selected according to the following 
specifications sheet. 
1 drive 2 type (18K outdoor unit) 
1 drive 3 type (27K outdoor unit). 
1 drive 4 type (36K outdoor unit) 
1 drive 5 type (48K outdoor unit) 
For indoor unit and outdoor unit connection 
line, 16AWG is ok for all. 
4.3 Pipe length and the elevation 
Maximum piping length and height difference 
Max. length for all 
rooms (m) 
Max. length for 
one IU (m) 
Max. height 
difference between 
IU and OU (m) 
Max. height 
difference between 
IUs (m) 
Additional refrigerant charge 
Pre-charge pipe 
length (m) 
Additiona
l 
refrigeran
t charge 
15 x 
(length 
for all 
rooms - 
15) 
15 x 
(length 
for all 
rooms – 
22.5) 
15 x 
(length 
for all 
rooms - 
30) 
15 x 
(length 
for all 
rooms – 
37.5) 
0.161 
x(length 
for all 
rooms – 
49.2) 
(0.161 
x(length 
for all 
rooms – 
73.8) 
0.161x(le
ngth for 
all rooms 
– 98.4) 
.0.161x(le
ngth for 
all rooms 
–123) 
 
Caution: 
●  Refrigerant  pipe  diameter  is  different 
according  to  indoor  unit  to  be  connected. 
When  using  the  extension  pipe,  refer  to  the 
tables below. 
●  When  refrigerant  pipe  diameter  is  different 
from that of the outdoor unit connector (18K 
indoor unit) an additional adapter is required. 
   
Extension pipe diameter 
(mm/inch) 
Outdoor unit union diameter (mm/inch) 
 
4.4 First-Time Installation 
Air and moisture in the refrigerant system cause 
the following problems:  
●  Increases in system pressure 
●  Increases in operating current 
●  Decreases in cooling and heating efficiency 
●  Blocks in capillary tubing caused by moisture 
in the refrigerant circuit freezing 
●  Corrosion  of  parts  in  the  refrigerant  system 
caused by water 
The indoor units and the pipes between 
indoor and outdoor units must be tested for 
leakages and evacuated to remove gas and 
moisture from the system. 
Gas leak check with soap water: 
Apply soap water or a liquid neutral 
detergent on the connections with a soft brush to 
check for leakage in the pipe connecting points. If 
bubbles emerge, the pipes are leaking. 
1. Air Purging Using the Vacuum Pump