21 
 
Increase fan speed increase
Keep current fan speed
Decrease fan speed
Fan stop
 
5.4.3.2 Heating Mode 
Under  normal  operating  conditions,  the  system 
chooses  a  running  fan  speed  according  to 
ambient temperature: 
 
5.4.4  Electronic Expansion Valve (EXV) 
Control 
1.  EXV  remains  fully  closed  while  the  device  is 
powering up.  EXV then remains on standby with 
350P open. It opens to the target angle after the 
compressor starts. 
2. EXV closes with -160P when the compressor 
stops.  Then  it  remains  on  standby  with  350P 
open.  It  opens  to  the  target  angle  after  the 
compressor starts. 
3. The action priority for the EXVs is A-B-C-D-E. 
4.  The  compressor  and  outdoor  fan  commence 
operation only after EXV initializes. 
5.4.4.1 Cooling Mode 
The initial open angle of the EXV depends on the 
size of the indoor model. The adjustment range is 
100-400p.  
 
When  the  unit  has  been  running  for  3  minutes, 
the  outdoor  receives  indoor  units'  capacity 
demand and T2B information and then calculates 
their average. After comparing each indoor’s T2B 
with the average, the outdoor gives the following 
modification commands: 
 
---- If the T2B>average, the relevant valve needs 
to open 16p more 
 
---- If the T2B= average, the relevant valve’s open 
range remains as is 
 
---- If the T2B<average, the relevant valve needs 
to close 16p more 
 
This modification is carried out every 2 minutes. 
 
5.4.4.2 Heating Mode 
The initial open angle of the EXV depends on the 
size of the indoor model. The adjustment range is 
150-350p.  
 
When  the  unit  has  been  running  for  3  minutes, 
the outdoor unit receives the indoor units' indoor 
units'  capacity  demand  and  T2  information  and 
then calculates their average.  
 
After  comparing  each  indoor  unit’s  T2  with  the 
average,  the  outdoor  gives  the  following 
modification commands: 
 
----If  the  T2 > average+2,  the  relevant  valve 
needs to close 16p more 
 
---- If average+2≥the T2≥ average-2, the relevant 
valve’s open range remains as is 
 
----If the T2<average-2, the relevant valve needs 
to open 16p more 
 
This modification is carried out every 2 minutes.