If the outdoor ambient temperature is higher than 
the set frequency during oil return, the unit stops 
the oil return process. 
 
5.3.11 Low Outdoor Ambient Temperature 
Protection 
When the compressor is off and T4 is lower than -
35℃ for 10 seconds, the unit stops and displays 
“LP.” 
When the compressor is on and T4 remains lower 
than -40℃ for 10 seconds, the unit stops and 
displays “LP.” 
When T4 is no lower than -32℃ for 10 seconds, 
the unit exits protection. 
 
 
5.4 Control and Functions 
5.4.1 Capacity Request  Calculation 
Cooling Mode: 
 
 
Note: The final result is an integer. 
Use  the  following  table  and  final  capacity 
request to confirm the operating frequency. 
Amendatory 
capacity 
demand. 
 
The maximum running frequency is adjusted 
according to the outdoor ambient temperature 
 
Heating Mode 
 
 
Note: The final result is an integer. 
Then  modify  it  according  to  a  T2  average 
(correction):