When the compressor discharge temperature(T5) is more 
than 115℃ for 10 seconds, the compressor will stop and 
restart till T5 is less than 90℃. 
Temperature protection of 
compressor discharge 
Temperature protection of 
compressor discharge 
Check whether the 
compressor discharge temp. is 
more than 115°C ?
Check whether the 
compressor discharge temp. is 
more than 115°C ?
Check  whether  the 
connection  is  right  between 
compressor discharge temp. 
sensor  and  PCB  according 
to wiring diagrams?
Check  whether  the 
connection  is  right  between 
compressor discharge temp. 
sensor  and  PCB  according 
to wiring diagrams?
Measure the resistance value 
of compressor discharge 
temp. sensor. If the value is 
not normal is normal refer to 
the Appendix 2?
Measure the resistance value 
of compressor discharge 
temp. sensor. If the value is 
not normal is normal refer to 
the Appendix 2?
No
Yes
Yes
No
Correct the wiring connection
Correct the wiring connection
Stop leaking and add refrigerant
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
Replace the compressor discharge temp. sensorNo
Yes
Replace high pressure valve assy
Replace high pressure valve assy
Yes
No
Replace outdoor main PCB
Replace outdoor main PCB
No
Check whether the 
refrigerant is leak
Check whether the 
refrigerant is leak