12 
 
 
1.  Completely  tighten  the  flare  nuts  on  the 
indoor  and  outdoor  units.  Confirm  that  both 
the2-way  and  3-way  valves  are  set  to  the 
closed position. 
2.  Connect the charge hose with the push pin of 
the Handle Lo to the 3-way valve gas service 
port. 
3.  Connect the charge hose of the Handle Hi to 
the vacuum pump. 
4.  Fully  open  the  Handle  Lo  of  the  manifold 
valve. 
5.  Turn  on  the  vacuum  pump  to  begin 
evacuation. 
6.  Conduct  a  30-minute  evacuation.  Check 
whether  the  compound  meter  indicates  -
0.1Mpa(14.5Psi).  If  the  meter  does  not 
indicate  -0.1Mpa(14.5Psi)  after  30  minutes 
has elapsed, continue evacuation for 20 more 
minutes.  If  the  pressure  does  not  reach  -
0.1Mpa(14.5Psi)  after  50  minutes  has 
elapsed, check if there are any leaks. 
Fully close the Handle Lo valve of the manifold 
valve and turn off the vacuum pump. After 5 
minutes, confirm that the gauge needle is not 
moving. 
7.  Turn  the  flare  nut  on  the  3-way  valve45° 
counterclockwise for  6-7 seconds.  Once gas 
begins  to  come  out,  tighten  the  flare  nut. 
Make  sure  the  pressure  display  on  the 
pressure indicator is higher than atmospheric 
pressure. Then remove the charge hose from 
the 3-way valve. 
8.  Fully  open  the  2-wayand  3-way  valves  and 
securely tighten the cap on the 3-way valve. 
 
2.  Adding  refrigerant  if  the  pipe  length 
exceeds chargeless pipe length  
 
Procedure: 
1) Connect the charge hose to the charging cylinder 
and open the 2-way and 3-way valves. 
With the charge hose you disconnected from the 
vacuum pump, connect it to the valve at the 
bottom of the cylinder. 
If the refrigerant is R410A, place the cylinder 
bottom-up to ensure liquid charging is possible. 
2). Purge the air from the charge hose. 
Open the valve at the bottom of the cylinder and 
press the check valve on the charge set (be 
careful of the liquid refrigerant). 
3) Place the charging cylinder onto the electronic 
scale and record the weight. 
4) Turn on the air conditioner in cooling mode. 
5)  Open  the  valves  (Low  side)  on  the  charge  set. 
Charge the system with liquid refrigerant. 
6).When  the  electronic  scale  displays  the  proper 
weight  (refer  to  the  table),  disconnect  the  charge 
hose  from  the  3-way  valve’s  service  port 
immediately  and  turn  off  the  air  conditioner  before 
disconnecting the hose. 
7). Mount the valve stem caps and the service port 
Use a torque wrench to tighten the service port 
cap to a torque of 18N.m(13.27 ft·lbs). 
Be sure to check for gas leaks.