IPM module protection
Check whether the voltage range 
of P-N on IPM module is normal? 
DC277-356V for 18-27KBtu/h; 
DC277-410V for 36-48KBtu/h
Yes
Yes
No
Yes
Check whether the input 
power supply is correct? 
208-230V, 1N, 60Hz
No No
Regulate it to correct, then 
check whether the system 
can work normally?
Check whether the 
power supply line is 
connected correctly and 
tightly
Yes
Connect it correctly 
and tightly, check ok 
or not?
No
Check whether the connecting 
line between main board and 
the IPM module is connected 
tightly
Yes
Connect it tightly, 
check ok or not?
No
No
No
Connect it well, check 
ok or not?
Check whether the connecting 
line of the compressor is 
connected correctly or tightly
Replace the IPM module, 
check whether the system can 
work normally?
No
No
Replace the main board; check 
whether the system can work 
normally?
No
Replace the compressor, check 
whether the system can work 
normally?
Check whether the lines 
in E-part box are 
connected tightly
Yes
Connect it tightly, 
check ok or not?
No
No
Yes
No
Replace the bridge rectifiers
Check whether the bridge rectifiers are 
normal? Use the multimeter to measure 
the resistance between each two 
terminals, check whether there is the 
condition that value of resistance is 0
Check  whether  the  connecting  line  of 
every  reactor  is  normal?  If  the  line  is 
broken, the resistance of the two ports is 
∞;Check  whether  the  PFC  module 
broken  (for  M4OF-36HFN1-M & M5OF-
48HFN1-M)
Replace the connecting line or 
reactor or replace the PFC 
module(for M4OF-36HFN1-
M&M5OF-48HFN1-M)
Yes
No
No
Yes
Trouble is solved
Check if the outdoor fan 
runs properly or the outdoor 
unit ventilation is good.
No
Refer to the solution of fan 
speed has been out of control 
malfunction . Find out the cause 
and have it solved.
Yes
Yes
Yes