Aqua Tempo Super II
201709 53
Part
4 - Diagnosis and Troubleshooting
4.4 E2 Troubleshooting
Digital display output 4.4.1
Description 4.4.2
Communication error between outdoor unit and user interface.
All units stop running.
Error code is displayed on main PCB and user interface.
Possible causes 4.4.3
Communication wires between outdoor unit and user interface not connected properly.
Communication wiring P Q E terminals misconnected.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged main PCB, user interface or electric control box communication terminals block.