Service Manual
4.18 PL Troubleshooting
Digital display output 4.18.1
Description 4.18.2
PL indicates inverter module temperature protection. When the main inverter module temperature rises above 82
o
C,
the system displays PL protection and all the units stop running. When the inverter module temperature drops below
60°C, the compressor enters re-start control
When a PL error occurs 3 times in 100 minutes, a manual system restart is required before the system can resume
operation.
Error code is displayed on the main PCB and user interface.
Possible causes 4.18.3
Blocked, dirty or loose heat sink.
Temperature sensor not connected properly or has malfunctioned.
Fan motor wiring connection is wrong.
Main PCB damaged.