4 - Diagnosis and Troubleshooting
4.9 P0 Troubleshooting
Digital display output 4.9.1
Description 4.9.2
Discharge pipe high pressure or discharge temperature switch protection. When the discharge pressure rises above
4.4MPa or discharge temperature rises above 115°C , the system displays P0 protection and all units stop running.
When the discharge pressure falls below 3.2MPa or discharge temperature fall below 75°C , P0 is removed and normal
operation resumes. When P0 error occurs 5 times in 120 minutes, a manual system restart is required before the
system can resume operation.
Error code is displayed on main PCB and user interface.
Possible causes 4.9.3
High pressure switch or discharge temperature switch not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.