EasyManua.ls Logo

Midea MC-SU30-RN1L

Midea MC-SU30-RN1L
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Aqua Tempo Super II
58 201709
Midea Aqua Tempo Super II
Service Manual
4.6 E9 Troubleshooting
Digital display output 4.6.1
Description 4.6.2
Water flow failure.
E9 indicates a water flow switch error. When an E9 error occurs 3 times in 60 minutes, a manual system restart is
required before the system can resume operation.
All units stop running.
Error code is displayed on main PCB and user interface.
Possible causes 4.6.3
The wire circuit is short connected or open.
Water flow rate is too low.
Water flow switch damaged.
Damaged main PCB.

Table of Contents

Other manuals for Midea MC-SU30-RN1L

Related product manuals