EasyManua.ls Logo

Midea MC-SU30-RN1L

Midea MC-SU30-RN1L
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Aqua Tempo Super II
84 201709
Midea Aqua Tempo Super II
Service Manual
4.17 PE Troubleshooting
Digital display output 4.17.1
Description 4.17.2
Water side heat exchanger low temperature protection.
All units stop running.
Error code is displayed on main PCB and user interface.
Possible causes 4.17.3
Temperature sensor not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange in heating mode.
Insufficient water flow in cooling mode.
Main PCB damaged.

Table of Contents

Other manuals for Midea MC-SU30-RN1L

Related product manuals