4.23 FP Troubleshooting
Digital display output 4.23.1
Description 4.23.2
FP indicates pump in a combination system dial to different status. When the FP displayed, a manual system restart is
required before the system can resume operation.
All units stop running.
Error code is only displayed on main PCB and user interface.
Possible causes 4.23.3
The S5_3 of slave units is different with the master unit.
Main PCB damaged.
Procedure 4.23.4
H6
The S5_3 of slave units is different with
the master unit
1
Yes
Adjust the switch of S5_3
No
Replace outdoor main PCB
Note:
1. Dial switch S5 on the main PCB (labeled 3 in Figure 4-2.1 in Part 4, 2.2 “Outdoor unit main PCB”)