EasyManuals Logo

Midea MC-SU30-RN1L Service Manual

Midea MC-SU30-RN1L
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #95 background imageLoading...
Page #95 background image
Aqua Tempo Super II
94 201709
Midea Aqua Tempo Super II
Service Manual
4.23 FP Troubleshooting
Digital display output 4.23.1
Description 4.23.2
FP indicates pump in a combination system dial to different status. When the FP displayed, a manual system restart is
required before the system can resume operation.
All units stop running.
Error code is only displayed on main PCB and user interface.
Possible causes 4.23.3
The S5_3 of slave units is different with the master unit.
Main PCB damaged.
Procedure 4.23.4
H6
The S5_3 of slave units is different with
the master unit
1
Yes
Adjust the switch of S5_3
No
Replace outdoor main PCB
Note:
1. Dial switch S5 on the main PCB (labeled 3 in Figure 4-2.1 in Part 4, 2.2 “Outdoor unit main PCB”)

Table of Contents

Other manuals for Midea MC-SU30-RN1L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MC-SU30-RN1L and is the answer not in the manual?

Midea MC-SU30-RN1L Specifications

General IconGeneral
BrandMidea
ModelMC-SU30-RN1L
CategoryChiller
LanguageEnglish

Related product manuals