2.17 Hb: Low pressure sensor error
Digital display output
Description
Low pressure sensor error.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: The main control board cannot receive the feedback signal of low pressure sensor.
Recover condition: The main control board can receive the feedback signal of low pressure sensor.
Reset method: Resume automatically.
Possible causes
Outdoor unit Low gas stop valves are closed.
Pressure sensor not connected properly or has malfunction.
Outdoor main PCB damaged.