V6R VRF 50Hz
98
Midea
V6R
Series Service Manual
2.10 F3, F5, F9, FA, Fb, Fc, Fd: T6B/T6A/T5/T8/T9/TL/T7 Temperature sensor error
Digital display output
Description
ï‚§ F3 indicates subcooling gas temperature sensor (T6B) error.
ï‚§ F5 indicates injection liquid temperature sensor (T6A) error.
ï‚§ F9 indicates liquid pipe temperature sensor (T5) error.
ï‚§ FA indicates heat exchanger gas temperature sensor (T8) error.
ï‚§ Fb indicates heat sink temperature sensor (T9) error.
ï‚§ Fc indicates heat exchanger liquid temperature sensor (TL) error.
ï‚§ Fd indicates suction temperature sensor (T7) error.
ï‚§ All units stop running.
ï‚§ Error code is displayed on the unit with the error.
Trigger / recover condition
ï‚§ Trigger condition: Temperature sensor T6A/T6B/T5/T7/T8/T9/TL is open or short-circuited.
ï‚§ Recover condition: Temperature sensor T6A/T6B/T5/T7/T8/T9/TL connection ports can detect load.
ï‚§ Reset method: Resume automatically.
Possible causes
ï‚§ Temperature sensor not connected properly or has malfunction.
ï‚§ Damaged outdoor main PCB.

Table of Contents

Other manuals for Midea MV6-R335WV2RN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV6-R335WV2RN1 and is the answer not in the manual?

Midea MV6-R335WV2RN1 Specifications

General IconGeneral
BrandMidea
ModelMV6-R335WV2RN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals